Remote IO Controller with Ethernet Port

InHand Networks SKU: INZ-IO-6042-I20
filler

Price:
$85
Use code: INHAND-20 to save $20 on all our cellular devices and switches.

Remote IO controller with Ethernet port

The remote IO control module based on Ethernet transmission , it support the conversion between Modbus TCP and Modbus RTU and supports virtual serial port functionality, it has 4 digital inputs, 2 analog input and 4 relay output.

features of 6042

Interested in this product?

Get Best Quote

IO Ports Description

Digital Inputs

It's compatible with passive switch(dry node) and active level(wet node), for the active level, wet mode, the voltage range as followed:

VCC Voltage Low Level Range High Level Range
24V 0-17V 17-24V
9V 0-3V 3-9V

Analog Inputs: multiple options

Current input : 4~20mA (INZ-IO-6042-I20)
Voltage input: 0~5V,0~10V (INZ-IO-6042-V5), (INZ-IO-6042-V10)
Resistance input: 0~10K (INZ-IO-6042-R10K)

Digital Outputs

Output type: relay output (5A@AC250V/DC30V)

Features

Support DHCP and DNS

The Remote IO Module supports DHCP and DNS to solve IP P management, IP conflict. It can fulfill telecommunication requirements through domain name..

DHCP, DNS

Modbus Communication

Connect the input and output devices on site to INZ-IO-6042, and then the INZ-IO-6042 connect to the Ethernet network, so the host computer could inquiry input signal of input devices and control the relay output of output devices.

industrial grade chip

Support Web interface and Device management tool to configure device

Technical Parameter

Figure
Size L x w x H = 12.2cm x 7.2cm x 3.4cm
Serial Port
RS485 port, 1200-115200bps (default 9600), 8bits, NONE parity, 1stop bit
Software
Upper Layer Protocol Modbus RTU/Modbus TCP
Physical Protocol Ethernet, RS485
Relay Transmission Time (Response time)
<30ms
AI Input Format
Current: 4-20mA, 0-20mA
Voltage: 0-5V, 0-10V
Resister: 0-10K, temperature/humidity sensor
Power Consumption
<1.8W, <75mA, @24V
Environment
Operating temperature -40 ~ 85℃
Storage temperature -45 ~ 165℃
Humidity 5 ~ 95% relative

Modbus Command Description

The remote I/O controller uses MODBUS TCP or RTU to communicate with PC software, Modbus register table defined as followed:

Register address No. of DI/DO/AI Modbus Command Descriptions R/W
00001 0 01 No. 1 DI Read Only
00002 1 01 No. 2 DI Read Only
00003 2 01 No. 3 DI Read Only
00004 3 01 No. 4 DI Read Only
00017 0 01/05 No. 1 DO Read/Write
00018 1 01/05 No. 2 DO Read/Write
00019 2 01/05 No. 3 DO Read/Write
00020 3 01/05 No. 4 DO Read/Write
30001 0 04 No. 1 AI Read Only
30002 1 04 No. 2 AI Read Only

Take for an example:
1.Single coil read command: 0x01
2.Input register read command: 0x04
3.Single coil write command: 0x05

single coil read command: 0x01
bytes 1 1 1 1 1 1 1 1
name address command Register addr high Register addr low Data len high Data len low CRC high CRC low

example: send-> 01 01 00 00 00 04 3d c9
recv->01 01 01 of 11 8c

read input register command:0x04
bytes 1 1 1 1 1 1 1 1
name address command Register addr high Register addr low Data len high Data len low CRC high CRC low

example: send-> 01 04 00 00 00 02 71 cb
recv->01 04 04 00 01 00 02 2b 85

single coil set command: 0x05
bytes 1 1 1 1 1 1 1 1
name address command Register addr high Register addr low Data len high Data len low CRC high CRC low

example: send-> 01 05 00 10 ff 00 8d ff
recv->01 05 00 10 ff 00 8d ff

Product Compare

                                                                                                                                                                                                                                                                                                                                                                                             
Remote IO Module
ModelINZ-IO-6042 INZ-IO-6002
Analog input2*AI2*AI
Digital input4*DI4*DI
Relay output4*DO4*DO
RJ45 Ethernet port-
RS485-

You may also like